1.1. Manual Operation

To set a pump in the HAND position, touch a pump HOA switch on the left side to select the mode. The pump will start after a 2 second delay. This delay prevents a pump from attempting to start while the HOA switch passes through the Hand position to reach other modes. The pump will run at the preset manual speed setting located in the lower right corner of the main operating screen. To change the speed, select the Manual Speed value, enter the desired % speed and touch ENTER. Pumps running in Hand will accelerate or decelerate to the new speed setting.


Only the Low Suction Alarm shuts down a pump running in Hand mode. If the pump does not start after the delay, touch Menu and then System Status. If the Low Suction alarm is active, touch Alarm Reset button to deactivate the alarm.
CAUTION: Running pumps in hand position overrides all system safeties and alarm shutdown features with except of low suction.